• DocumentCode
    1216533
  • Title

    Analyses of Axial Energy Distribution in Decaying Arc of SF6 Gas Circuit Breaker

  • Author

    Ikeda, H. ; Ishikawa, M. ; Yanabu, S.

  • Volume
    14
  • Issue
    4
  • fYear
    1986
  • Firstpage
    395
  • Lastpage
    401
  • Abstract
    Adopting a transient arc analyzing program, the authors analyzed the axial distribution of arc characteristics near the current-zero point, proving that while almost all portions of total arc resistance were shouldered in downstream arc, zero conductivity was achieved in the nozzle throat arc. It was also proved that in the presence of transient recovery voltage (TRV) with initial fluctuations, such as initial TRV (ITRV), an interruption was accomplished by combined effects of the downstream and the nozzle throat arc.
  • Keywords
    Circuit breakers; Circuit faults; Dielectric breakdown; Electric breakdown; Fluctuations; Fluid flow; Sulfur hexafluoride; Thermodynamics; Transient analysis; Voltage;
  • fLanguage
    English
  • Journal_Title
    Plasma Science, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-3813
  • Type

    jour

  • DOI
    10.1109/TPS.1986.4316567
  • Filename
    4316567