DocumentCode :
1216533
Title :
Analyses of Axial Energy Distribution in Decaying Arc of SF6 Gas Circuit Breaker
Author :
Ikeda, H. ; Ishikawa, M. ; Yanabu, S.
Volume :
14
Issue :
4
fYear :
1986
Firstpage :
395
Lastpage :
401
Abstract :
Adopting a transient arc analyzing program, the authors analyzed the axial distribution of arc characteristics near the current-zero point, proving that while almost all portions of total arc resistance were shouldered in downstream arc, zero conductivity was achieved in the nozzle throat arc. It was also proved that in the presence of transient recovery voltage (TRV) with initial fluctuations, such as initial TRV (ITRV), an interruption was accomplished by combined effects of the downstream and the nozzle throat arc.
Keywords :
Circuit breakers; Circuit faults; Dielectric breakdown; Electric breakdown; Fluctuations; Fluid flow; Sulfur hexafluoride; Thermodynamics; Transient analysis; Voltage;
fLanguage :
English
Journal_Title :
Plasma Science, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-3813
Type :
jour
DOI :
10.1109/TPS.1986.4316567
Filename :
4316567
Link To Document :