DocumentCode
1216533
Title
Analyses of Axial Energy Distribution in Decaying Arc of SF6 Gas Circuit Breaker
Author
Ikeda, H. ; Ishikawa, M. ; Yanabu, S.
Volume
14
Issue
4
fYear
1986
Firstpage
395
Lastpage
401
Abstract
Adopting a transient arc analyzing program, the authors analyzed the axial distribution of arc characteristics near the current-zero point, proving that while almost all portions of total arc resistance were shouldered in downstream arc, zero conductivity was achieved in the nozzle throat arc. It was also proved that in the presence of transient recovery voltage (TRV) with initial fluctuations, such as initial TRV (ITRV), an interruption was accomplished by combined effects of the downstream and the nozzle throat arc.
Keywords
Circuit breakers; Circuit faults; Dielectric breakdown; Electric breakdown; Fluctuations; Fluid flow; Sulfur hexafluoride; Thermodynamics; Transient analysis; Voltage;
fLanguage
English
Journal_Title
Plasma Science, IEEE Transactions on
Publisher
ieee
ISSN
0093-3813
Type
jour
DOI
10.1109/TPS.1986.4316567
Filename
4316567
Link To Document