• DocumentCode
    1218376
  • Title

    Calculation of the induced effects due to a lightning stroke

  • Author

    Cristina, S. ; Orlandi, A.

  • Author_Institution
    Dept. of Electr. Eng., l´´Aquila Univ., Italy
  • Volume
    139
  • Issue
    4
  • fYear
    1992
  • fDate
    7/1/1992 12:00:00 AM
  • Firstpage
    374
  • Lastpage
    380
  • Abstract
    A method for computing the effects of a direct lightning stroke on the protection system of an industrial building is presented. The proposed method is based on a `circuit-approach´. The lightning protection system and the `victim´ circuits are simulated by means of an equivalent electrical network formed by resistances, inductances and capacitances, having all the branches coupled together. The lightning stroke is simulated by means of an ideal current source characterised by a pulse waveshape. Propagation phenomena are considered and the ionisation phenomena in the soil are taken into account by a nonlinear current-dependent electrical model, function of the electrode´s shape and the ground resistivity. Two distinct points of impact of the lightning stroke to the protection system are considered. An analysis, in the frequency and in the time domain, of effects such as step voltages of EMF induced on power cables, coaxial cables, and loops is performed
  • Keywords
    electromagnetic induction; electromagnetic interference; lightning; transients; capacitances; coaxial cables; discharges; equivalent electrical network; frequency-domain analysis; ideal current source; induced EMF; inductances; industrial building; interference; lightning protection system; lightning stroke effects; power cables; pulse waveshape; resistances; soil ionisation phenomena; step voltages; time-domain analysis; transient effects;
  • fLanguage
    English
  • Journal_Title
    Electric Power Applications, IEE Proceedings B
  • Publisher
    iet
  • ISSN
    0143-7038
  • Type

    jour

  • Filename
    153403