DocumentCode :
1219716
Title :
Partial discharges in 3-core belted power cables
Author :
Harking, E. ; Kreuger, F.H. ; Morshuis, P.H.F.
Author_Institution :
High Voltage Lab., Tech. Univ. Delft, Netherlands
Volume :
24
Issue :
4
fYear :
1989
fDate :
8/1/1989 12:00:00 AM
Firstpage :
591
Lastpage :
598
Abstract :
It is noted that partial discharge testing of three-core belted-type cable using single-phase test voltage may lead to large errors as compared to the actual three-phase service conditions. The method of energizing the cable and the configuration of the discharge detection circuit largely affect the magnitude of the error. Eight different test circuits are discussed with respect to their usefulness in the laboratory as well as the field. Attention is paid to the similarity of the electrical stresses in the single and three-phase circuits. To this purpose field calculations were performed on different single-phase test circuits to determine a design that meets the three-phase field patterns at its best. Three circuits are selected as being suitable for a correct single-phase partial discharge measurement
Keywords :
cable insulation; cable testing; insulation testing; partial discharges; power cables; discharge detection circuit; electrical stresses; field calculations; partial discharge testing; single-phase test voltage; three-core belted-type cable; three-phase service conditions; Belts; Cable insulation; Circuit testing; Laboratories; Partial discharge measurement; Partial discharges; Permittivity; Power cables; Stress; Voltage;
fLanguage :
English
Journal_Title :
Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9367
Type :
jour
DOI :
10.1109/14.34193
Filename :
34193
Link To Document :
بازگشت