DocumentCode
1220673
Title
Optimal choice of fixed and switched capacitors in radial distributors with distorted substation voltage
Author
Wu, Z.Q. ; Lo, K.L.
Author_Institution
Dept. of Electr. Eng., Hunan Univ., Changsha, China
Volume
142
Issue
1
fYear
1995
fDate
1/1/1995 12:00:00 AM
Firstpage
24
Lastpage
28
Abstract
The problem of optimal choice of fixed and switched capacitors in radial distributors with distorted substation voltages is formulated and solved by decomposition through isolated subproblems. The maximum sensitivities selection (MSS) method, which is used to solve the optimisation problem of the subproblems with discrete variables, is proposed. The results of a test distributor show that harmonic voltages in the substation voltage affects the capacitance of the optimal shunt capacitors. By combining system harmonic forecasting with the method in this paper, the harmonics amplification due to shunt capacitors can be reduced to the minimum level
Keywords
capacitance; compensation; distribution networks; harmonic distortion; losses; optimisation; power capacitors; power system harmonics; substations; capacitance; decomposition; discrete variables; distorted substation voltage; distribution networks; fixed capacitors; harmonic voltages; harmonics amplification; isolated subproblems; losses compensation; maximum sensitivities selection method; optimal choice; optimisation; radial distributors; shunt capacitors; switched capacitors; system harmonic forecasting;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings-
Publisher
iet
ISSN
1350-2360
Type
jour
DOI
10.1049/ip-gtd:19951570
Filename
342243
Link To Document