Author :
Kopplin, H. ; Motschmann, H. ; Rolff, K.P. ; Zückler, K.
Abstract :
The article deals with studies of the arcing performance of SF6 puffer breakers at currents of up to 80 kA and voltages of up to 200 kV, using an interrupter unit fitted with viewing windows. The studies are mainly concerned with the behavior of the arc at current zero and with restrike phenomena under various conditions. In addition to measurements of the electrical variables and the pressure variation, the tests cover the use of high-speed cameras, spectroscopic diagnostic methods, and schlieren methods. The density fields and flow fields derived from the latter are used to optimize the gas flow. On the basis of the breaker data and those of its operating mechanism a method for computing the essential variables, e.g., pressure, gas flow, back pressure, and contact travel, is developed. The variation of these parameters as a function of the interrupter data for various currents and with due allowance for the interaction between the arc and the operating mechanism must be known if the breaker design is to be optimized. The method uses simplified equations for the gas flow and the arc. The relationship between the gas data (e. g., density, enthalpy, speed of sound, electrical conductivity, and dielectric strength) and the temperature is taken into account by using approximation functions. The temperature of the arc core is matched to the test results.