Title
Optimum compression ratio on ground grid design in MEA´s power distribution substation
Author
Phayomhom, A. ; Sirisumrannukul, S. ; Kasirawat, T. ; Puttarach, A.
Author_Institution
Power Syst. Planning Dept., Metropolitan Electr. Authority, Bangkok, Thailand
fYear
2014
fDate
19-21 March 2014
Firstpage
1
Lastpage
4
Abstract
The study provides comparison of grounding performance between square and rectangle ground grid, when given the same size of area of coverage. The result shows that the rectangle ground grid possesses better grounding performance than the square one. The study also finds the optimum compression ratio (OCR) of both grounding configuration. The OCR of square and rectangle ground grids are found to be 0.3 and 0.4 respectively. Modeling and simulation is carried out on the Current Distribution Electromagnetic interference Grounding and Soil structure (CDEGS) program. The simulation results support the fact that unequal span ground grid is more superior to the equal span type. The finding could be used as a guide line in grounding grid design.
Keywords
earthing; power distribution protection; power grids; substation protection; CDEGS program; Current Distribution Electromagnetic interference Grounding and Soil structure program; MEA power distribution substation; OCR; ground grid design; optimum compression ratio; rectangle ground grid; square ground grid; Ground penetrating radar; Grounding; Indexes; Optical character recognition software; Steel; Apparent resistivity; Ground potential rise; Optimum compression ratio; Step voltage; Touch voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Engineering Congress (iEECON), 2014 International
Conference_Location
Chonburi
Type
conf
DOI
10.1109/iEECON.2014.6925843
Filename
6925843
Link To Document