• DocumentCode
    122567
  • Title

    Optimum compression ratio on ground grid design in MEA´s power distribution substation

  • Author

    Phayomhom, A. ; Sirisumrannukul, S. ; Kasirawat, T. ; Puttarach, A.

  • Author_Institution
    Power Syst. Planning Dept., Metropolitan Electr. Authority, Bangkok, Thailand
  • fYear
    2014
  • fDate
    19-21 March 2014
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The study provides comparison of grounding performance between square and rectangle ground grid, when given the same size of area of coverage. The result shows that the rectangle ground grid possesses better grounding performance than the square one. The study also finds the optimum compression ratio (OCR) of both grounding configuration. The OCR of square and rectangle ground grids are found to be 0.3 and 0.4 respectively. Modeling and simulation is carried out on the Current Distribution Electromagnetic interference Grounding and Soil structure (CDEGS) program. The simulation results support the fact that unequal span ground grid is more superior to the equal span type. The finding could be used as a guide line in grounding grid design.
  • Keywords
    earthing; power distribution protection; power grids; substation protection; CDEGS program; Current Distribution Electromagnetic interference Grounding and Soil structure program; MEA power distribution substation; OCR; ground grid design; optimum compression ratio; rectangle ground grid; square ground grid; Ground penetrating radar; Grounding; Indexes; Optical character recognition software; Steel; Apparent resistivity; Ground potential rise; Optimum compression ratio; Step voltage; Touch voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Engineering Congress (iEECON), 2014 International
  • Conference_Location
    Chonburi
  • Type

    conf

  • DOI
    10.1109/iEECON.2014.6925843
  • Filename
    6925843