Abstract :
This paper addresses the issue of determining the level of defect that is likely to cause the failure of solid dielectric transmission class cables. It also proposes methods for predicting the level of defect that is likely to cause failure and to provide a simple analytic approximation for doing so in the case of conducting spheroids aligned with the electric field. A common assumption is that conducting particles > 100 μm in length are likely to cause failure of extruded dielectric transmission cable. This analysis suggests that when the effects of operation at elevated temperature are included in the analysis, this is probably an appropriate criterion with a sound technical basis. For maximum background fields in the range of 15 kV/mm, as presently seen near the conductor shield of some transmission class cables, a worst-case particle length in the range of 0.1 mm is likely to be required to cause failure for the worst-case local polymer morphology in the range of the maximum operating temperature.
Keywords :
dielectric materials; failure analysis; power cables; power transmission faults; power transmission lines; conductor shield; defect tolerance; extruded dielectric transmission cable; polymer morphology; solid dielectric transmission class cable; Conductivity; Dielectrics; Distributed computing; Polymers; Power industry; Power system reliability; Solids; Statistics; Substations; Voltage;
fLanguage :
English
Journal_Title :
Electrical Insulation Magazine, IEEE
Publisher :
ieee
ISSN :
0883-7554
Type :
jour
DOI :
10.1109/MEI.2005.1389268
Filename :
1389268
Link To Document :
بازگشت