• DocumentCode
    122611
  • Title

    Investigation of active power measurements in harmonic conditions

  • Author

    Kochawat, Tanya ; Phapukdee, Voraphol

  • Author_Institution
    Electr. Metrol. Dept., Nat. Inst. of Metrol. (Thailand), Pathumthani, Thailand
  • fYear
    2014
  • fDate
    19-21 March 2014
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    An investigation of active power measurements using 4 different accuracy level watt meters when specific harmonic conditions (different harmonic currents, 4 values of fundamental power factor (PF) and no phase shift between harmonic voltages and harmonic currents) in the system was performed. Expected active powers during harmonic environments based on IEEE Std. 1459-2010 were calculated to be reference powers. Results show the reference and working level watt meters provide measured active powers perfectly while the general measuring watt meter gives a large error especially when a harmonic content is high but a PF is very low. Thus, uses of active power values in harmonic conditions obtained from watt meters need to be careful particularly those obtained from general measuring watt meters.
  • Keywords
    IEEE standards; power factor; power measurement; power system harmonics; wattmeters; IEEE Std. 1459-2010; PF; active power measurements; active power values; harmonic conditions; harmonic currents; harmonic environments; harmonic voltages; power factor; watt meters; Abstracts; Area measurement; Atmospheric measurements; Distortion measurement; Harmonic analysis; Monitoring; Particle measurements; harmonic active power; watt meter;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Engineering Congress (iEECON), 2014 International
  • Conference_Location
    Chonburi
  • Type

    conf

  • DOI
    10.1109/iEECON.2014.6925887
  • Filename
    6925887