Title :
Aging of 154 kV underground power cable insulation under combined thermal and electrical stresses
Author :
Aras, Faruk ; Alekperov, Vilayed ; Can, Nursel ; Kirkici, Hulya
Author_Institution :
Kocaeli Univ., Kocaeli
Abstract :
This work the combined electrical and thermal stresses of the 154 kV XLPE power cable used in the underground power transmission in Turkey. The dependence of aging on electrical and thermal stresses is given by a straight line in a certain range of electric field (E) values which indicates that the aging is a thermochemical process. Furthermore, cable tests are conducted in oil, and the results are valid for immersed insulation but might not be completely representative of XLPE used in service in a "dry" environment. Therefore, each cable insulator has to be tested and the parameters must be determined for each cable separately.
Keywords :
XLPE insulation; ageing; power cable insulation; power cable testing; underground cables; Turkey; XLPE insulation; aging; cable testing; electrical stress; oil immersed insulation; thermal stress; thermochemical process; underground power cable insulation; voltage 154 kV; Aging; Cable insulation; Dielectrics and electrical insulation; Insulation testing; Oil insulation; Petroleum; Power cables; Power transmission; Thermal stresses; Underground power cables;
Journal_Title :
Electrical Insulation Magazine, IEEE
DOI :