Title :
A new algorithm enabling controlled short circuit interruption
Author :
Pöltl, Anton ; Fröhlich, Klaus
Author_Institution :
ABB Inc., Mt. Pleasant, PA, USA
fDate :
7/1/2003 12:00:00 AM
Abstract :
Controlled interruption of short circuit currents in medium- and high-voltage systems by means of point-on-wave control has not been feasible so far for technical reasons. The determination of the optimal tripping moment to achieve minimal contact wear should not take more time than the protection relay takes to indicate the fault, which makes it a difficult problem. As a solution, a so-called safe-point algorithm was developed, which overcomes the problem by an approximation of sufficient accuracy and with a time request of not much more than half a cycle of the power frequency. Computer simulations demonstrate that the mean I2t can be reduced significantly. The method provides the foundation for implementing controlled switching of fault currents.
Keywords :
fault currents; power system protection; power system simulation; relay protection; short-circuit currents; switching; computer simulations; controlled short circuit interruption; high-voltage systems; medium-voltage systems; minimal contact wear; optimal tripping moment; point-on-wave control; power frequency; protection relay; safe-point algorithm; short circuit currents; Approximation algorithms; Circuit faults; Computer simulation; Control systems; Fault currents; Frequency; Power system protection; Power system relaying; Protective relaying; Short circuit currents;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2003.813635