DocumentCode
1227568
Title
Medium voltage distribution systems lightning performance estimation
Author
Savic, Milan S.
Author_Institution
Fac. of Electr. Eng., Univ. of Belgrade, Yugoslavia
Volume
18
Issue
3
fYear
2003
fDate
7/1/2003 12:00:00 AM
Firstpage
910
Lastpage
914
Abstract
The estimation method for the statistical approach to the number of distribution system insulation failures caused by direct and indirect lightning strikes based on the lightning limiting parameter method is proposed. The optimal computation parameters like computation time-step, the number of strike locations along and perpendicular to the overhead line, and the number of simulations with different lightning current wave-shapes are determined after sensitivity analyses. The reduction of the overhead line flashover rate due to the direct lightning strikes caused by screening effect of the nearby objects is presented.
Keywords
flashover; insulation; lightning protection; overvoltage protection; power distribution lines; power overhead lines; sensitivity analysis; shielding; computation time-step; direct lightning strikes; distribution system insulation failures; indirect lightning strikes; induced overvoltage; lightning current wave-shapes; lightning limiting parameter method; lightning performance estimation; medium voltage distribution system; overhead line; overhead line flashover rate reduction; sensitivity analyses; shielding effect; statistical approach; strike locations; Cable insulation; Computational modeling; Conductors; Flashover; Lightning; Medium voltage; Phase estimation; Power transformer insulation; Substations; Surges;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2003.813860