DocumentCode
1227823
Title
Voltage and lamp flicker issues: should the IEEE adopt the IEC approach?
Author
Halpin, S. Mark ; Bergeron, Roger ; Blooming, Tom M. ; Burch, Reuben F. ; Conrad, Larry E. ; Key, Thomas S.
Author_Institution
Dept. of Electr. & Comput. Eng., Auburn Univ., Montgomery, AL, USA
Volume
18
Issue
3
fYear
2003
fDate
7/1/2003 12:00:00 AM
Firstpage
1088
Lastpage
1097
Abstract
This paper is intended to provide an overview of the IEC flicker measurement and assessment procedures. The IEC procedures are correlated with existing IEEE flicker standards to show the benefits of the IEC methodology. Application issues, such as customer impact assessment, are also discussed. Three case studies, two field tests, and one EMTP analysis are provided to show the correlation of IEC flickermeter output values with documented customer complaints. The case studies also provide areas where modifications to the IEC flicker standards may be necessary when developing a new IEEE flicker standard.
Keywords
IEC standards; IEEE standards; harmonic distortion; lamps; power supply quality; power system harmonics; IEC flicker assessment; IEC flicker measurement; IEC flicker standards; IEEE flicker standards; Lamp Flicker; application issues; case studies; customer impact assessment; voltage flicker; Associate members; EMTP; Frequency; IEC standards; Instruments; Lamps; Standards development; Testing; Threshold voltage; Voltage fluctuations;