    Distance relaying of 11 kV circuits to increase the installed capacity of distributed generation

  • Author

    Chilvers, I. ; Jenkins, N. ; Crossley, P.

  • Author_Institution
    Dept. of Electr. Eng. & Electron., Univ. of Manchester Inst. of Sci. & Technol.
  • Volume
    152
  • Issue
    1
  • fYear
    2005
  • Firstpage
    40
  • Lastpage
    46
  • Abstract
    The connection of generation to distribution networks may cause problems with existing protection schemes, while development of new protection schemes can facilitate an increase in generation capacity. The design and evaluation of a distribution network protection scheme based on distance relays is described. The scheme provides primary and back-up protection of 11 kV circuits. In the UK, voltage transformers and communication schemes are seldom installed on 11 kV circuits. Hence the distance relay restraint signal (voltage) is measured at the secondary winding of a distribution transformer (11/0.433 kV) to reduce costs. The development of the distance relay algorithm is discussed and a selection of simulation test results provided to illustrate the relay performance under fault conditions
  • Keywords
    cost reduction; distributed power generation; fault location; power distribution protection; power system relaying; power transformers; relay protection; transformer windings; voltage measurement; 0.433 kV; 11 kV; back-up protection; cost reduction; distance relaying; distributed generation installed capacity; distribution network protection; distribution transformer; fault condition; generation capacity; secondary winding; voltage measurement; voltage transformer;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:20041205
  • Filename
    1393416