• DocumentCode
    1234751
  • Title

    Double-iterative algorithm for the analysis of power and harmonic flows at AC/DC convertor terminals

  • Author

    Arrillaga, J. ; Callaghan, C.D.

  • Author_Institution
    Dept. of Electr. Eng., Canterbury Univ., Christchurch, New Zealand
  • Volume
    136
  • Issue
    6
  • fYear
    1989
  • fDate
    11/1/1989 12:00:00 AM
  • Firstpage
    319
  • Lastpage
    324
  • Abstract
    The accuracy of the formulation of the convertor models normally used in single-phase and three-phase AC/DC loadflows is restricted by the assumptions of perfectly smooth direct currents and of perfectly sinusoidal commutating voltages. Conversely, the harmonic current injections from convertor plant are calculated from nominal and generally symmetrical conditions and are thus unreliable. An algorithm integrating load-flow and harmonic analysis is proposed in which these assumptions are not made, thus allowing evaluation of their effect on the fundamental and harmonic flow solutions. It is shown that the interaction between the harmonic and load flows cannot be ignored even in the presence of filters, particularly when the convertor plant or AC system parameters are unbalanced
  • Keywords
    iterative methods; load flow; power convertors; power systems; 3-phase AC-DC load flow; AC/DC convertor terminals; double-iterative algorithm; harmonic analysis; harmonic current injections; power systems; single-phase AC-DC load flow;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • Filename
    35446