DocumentCode :
1235723
Title :
Aging of distribution cables in service and its simulation in the laboratory
Author :
Dalal, S.B. ; Gorur, R.S. ; Dyer, M.L.
Author_Institution :
Dept. of Electr. Eng., Arizona State Univ., Tempe, AZ
Volume :
12
Issue :
1
fYear :
2005
Firstpage :
139
Lastpage :
146
Abstract :
This study focuses on efforts to characterize aging occurring in 15 kV distribution cables in a dry climate. It has been shown that similar changes can be produced by a suitably planned accelerated thermal aging testing in the laboratory. The Arrhenius equation is used for establishing the accelerated aging test parameters. Different modes of statistical analysis namely analysis of variance (ANOVA), Andersen-Darling test for normality, F-test, t-test are performed to validate results from accelerated aging tests with field aging
Keywords :
XLPE insulation; ageing; distribution networks; insulation testing; life testing; power cable insulation; power cable testing; statistical analysis; thermal analysis; 15 V; ANOVA; Andersen-Darling test; Arrhenius equation; F-test; accelerated aging tests; aging simulation; distribution cable aging; statistical analysis; t-test; thermal aging testing; variance analysis; Accelerated aging; Analysis of variance; Cable insulation; Chemicals; Equations; Laboratories; Rivers; Temperature; Testing; Thermal stresses;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2005.1394024
Filename :
1394024