    Comparison of waveshape quality of artificial lines used for short-line fault breaking tests on HV circuit breakers

  • Author

    St-Jean, Guy ; Landry, Michel

  • Author_Institution
    Inst. de Recherche d´´Hydro-Quebec, Varennes, Que., Canada
  • Volume
    4
  • Issue
    4
  • fYear
    1989
  • fDate
    10/1/1989 12:00:00 AM
  • Firstpage
    2109
  • Lastpage
    2113
  • Abstract
    The authors present a comparison of the waveshape quality of six different artificial-line circuits used to produce the high rate-of-rise of recovery voltage specified by ANSI and IEC standards. For a purely capacitive and inductive pi-section circuit, it is shown that even eight pi sections do not meet the requirements. With the addition of a resistance in the first branch, this circuit design produces adequate solutions but requires a large number of components. The analysis reveals that the KEMA circuit easily meets the requirements for the rated peak factor of 1.6 but for the 1.8 peak factor a compensation would be required for the initial part of the wave. The simplest circuit comprising only three (RLC) components meets the specifications with a high voltage-peak overstress factor of 1.3
  • Keywords
    circuit breakers; electrical faults; switchgear testing; HV circuit breakers; artificial lines; capacitive pi-section circuit; inductive pi-section circuit; recovery voltage; short-line fault breaking tests; standards; waveshape quality; Capacitors; Circuit breakers; Circuit testing; DC generators; Delay effects; Impedance; Inductance; Power generation; Surges; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.35637
  • Filename
    35637