    Experimental study of response of power distribution lines to direct lightning hits

  • Author

    Yokoyama, S. ; Asakawa, A.

  • Author_Institution
    Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
  • Volume
    4
  • Issue
    4
  • fYear
    1989
  • fDate
    10/1/1989 12:00:00 AM
  • Firstpage
    2242
  • Lastpage
    2248
  • Abstract
    In order to clarify the response of overhead distribution lines to direct lightning hits, experimental facilities were installed at the UHV Shiobara Testing Laboratory of CRIEPI. A lightning impulse current with a crest value of 18 kA and a waveform of (2/11) μs was generated through the impulse current generator with a high internal resistance of 400 Ω. This impulse current is not easily affected by the conditions of a distribution line side. Protective effects of surge arresters and an overhead ground wire against direct strokes to the pole of a distribution line were clarified experimentally. Experimental results showed a better protective effect than earlier calculated results. Overvoltages between a line conductor and the earth are inclined to have a short wavetail. The 50% flashover voltage of an insulator against overvoltages with a short wavetail is higher than that against overvoltages with a standard wavetail
  • Keywords
    distribution networks; flashover; lightning; power overhead lines; surge protection; 18 kA; 400 ohm; UHV Shiobara Testing Laboratory of CRIEPI; direct lightning hits; flashover voltage; impulse current generator; lightning impulse current; line conductor; overhead distribution lines; overhead ground wire; overvoltage; surge arresters; Arresters; Conductors; Earth; Flashover; Laboratories; Lightning; Power distribution lines; Surge protection; Testing; Wire;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.35653
  • Filename
    35653