Influences of superconducting fault current limiter (SFCL) on superconducting generator in one-machine double-line system
Author :
Muta, Itsuya ; Doshita, Takeyuki ; Nakamura, Taketsune ; Egi, Toshiaki ; Hoshino, Tsutomu
Author_Institution :
Dept. of Electr. Eng., Kyoto Univ., Japan
Volume :
13
Issue :
2
fYear :
2003
fDate :
6/1/2003 12:00:00 AM
Firstpage :
2206
Lastpage :
2209
Abstract :
Analysis of superconducting generator in single machine double-line infinite-bus transmission system equipped with SFCL´s has been performed by use of EMTDC/PSCAD. When some faults occur in one transmission line, the SFCL in the fault line operates and then the peak fault current can be limited to expected value by use of a function of the SFCL. However, in some cases, the SFCL in the other sound line has been also proved to occasionally operate due to the interaction through each transmission line. Problems due to an installation of the SFCL´s in such a model system and the influences on the superconducting generator have been pointed out by simulation analysis.
Keywords :
AC generators; fault current limiters; power transmission lines; superconducting machines; EMTDC/PSCAD simulation analysis; single-machine double-line infinite-bus transmission system; superconducting fault current limiter; superconducting generator; transmission line; Circuit faults; Circuit simulation; Fault current limiters; PSCAD; Power system modeling; Power system simulation; Power system transients; Power transmission lines; Research and development; Superconducting transmission lines;
fLanguage :
English
Journal_Title :
Applied Superconductivity, IEEE Transactions on
Publisher :
ieee
ISSN :
1051-8223
Type :
jour
DOI :
10.1109/TASC.2003.813037
Filename :
1212057
Link To Document :
بازگشت