DocumentCode
1247136
Title
Calculating the switching surge critical flashover voltage of phase-to-ground and phase-to-phase bundle conductor gaps
Author
Podporkin, G.V.
Author_Institution
St. Petersburg State Tech. Univ., Russia
Volume
10
Issue
1
fYear
1995
fDate
1/1/1995 12:00:00 AM
Firstpage
365
Lastpage
373
Abstract
The paper presents a method for calculating the 50% breakdown voltages of conductor-to-plane and conductor-to-conductor air gaps for any bundle design, all the three phases of lines being taken into account. The method is developed for switching impulses with long time front (τf=1000-4000 μsec) which are the most typical for UHV lines. The results of calculations are extensively compared with previous experimental results for different bundles and over a wide range of gap spacings. The influence of bundle configuration, type of phases displacement (flat, delta or inverted delta) and voltage distribution among phases for UHV lines are analyzed
Keywords
air gaps; electric breakdown; flashover; overhead line conductors; power transmission lines; surges; switching; 50% breakdown voltages; UHV lines; air gaps; bundle configuration; delta displacement; flat displacement; inverted delta displacement; phase-to-ground conductor gap; phase-to-phase bundle conductor gap; phases displacement; switching impulses; switching surge critical flashover voltage; voltage distribution; Air gaps; Conductors; Corona; Electric breakdown; Electrodes; Flashover; Insulation; Power transmission lines; Surges; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.368377
Filename
368377
Link To Document