DocumentCode :
1247205
Title :
Above ground detection and interpretation of transient signals on underground power distribution systems
Author :
Weeks, Walter L. ; Steiner, J.P.
Author_Institution :
Purdue Univ., West Lafayette, IN, USA
Volume :
10
Issue :
1
fYear :
1995
fDate :
1/1/1995 12:00:00 AM
Firstpage :
69
Lastpage :
77
Abstract :
A relatively simple system for recording any high voltage/current transients that occur on underground power distribution systems is described. Experimental data resulting from faults on two different 15 kV class URD systems with helical neutrals is presented. A procedure for and discussion of the interpretation of the data is also presented in some detail. The most obvious application is for immediate fault location but the reproducibility of the data suggests other applications
Keywords :
distribution networks; fault location; power system measurement; power system transients; transient analysis; underground residential distribution systems; 15 kV; URD systems; above ground detection; fault location; helical neutrals; high current transients; high voltage transients; power distribution systems; transient signals detection; transient signals interpretation; Cable shielding; Circuit faults; Connectors; Power cables; Power distribution; RF signals; Reproducibility of results; Surges; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.368414
Filename :
368414
Link To Document :
بازگشت