DocumentCode :
1247207
Title :
The condition monitoring of fluid-filled taped cables employed in underground transmission through dissolved gas analysis
Author :
Singh, Nirmal ; Morel, Oscar E. ; Singh, Sandeep K. ; Rodenbaugh, Thomas J.
Author_Institution :
Detroit Edison Co., MI, USA
Volume :
10
Issue :
1
fYear :
1995
fDate :
1/1/1995 12:00:00 AM
Firstpage :
62
Lastpage :
68
Abstract :
There is an urgent need to monitor the condition of fluid-filled taped (FFT) cables. The dissolved-gas analysis (DGA) technique that has been successfully applied to power transformers holds great potential for the preventive maintenance of FFT cables. However, before this emerging technique can be properly applied to cables, a suitable fluid sampling and subsequent gas analysis method had to be developed, including the generation of both laboratory and field data to aid in data interpretation. Data on gas saturation levels in various cable fluids have been presented. This paper describes a novel method developed specifically for FFT cables and discusses field results so obtained. The type, distribution and concentration of gases from fluid alone and paper alone under electrical stress has been presented, including the differences between normal and not-so-normal cable systems as demonstrated by DGA. The concept of wet tensile strength has been introduced to the cable industry and it holds promise to serve as a cable aging indicator. DGA can successfully identify problem cable systems. Further work is in progress to refine the DGA technique and determine the remaining life of taped cables
Keywords :
chemical analysis; chemical variables measurement; insulating oils; insulation testing; life testing; monitoring; paper; power cable insulation; power cable testing; power cables; stress analysis; tensile strength; underground cables; underground transmission systems; cable aging indicator; condition monitoring; dissolved gas analysis; electrical stress; fluid sampling; fluid-filled taped cables; gas concentration; gas distribution; gas saturation levels; power transformers; preventive maintenance; remaining life determination; underground transmission; wet tensile strength; Cables; Condition monitoring; Dissolved gas analysis; Gases; Laboratories; Power transformers; Preventive maintenance; Sampling methods; Tensile stress; Voltage transformers;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.368415
Filename :
368415
Link To Document :