• DocumentCode
    1247215
  • Title

    An assessment of field aged 15 and 35 kV ethylene propylene rubber insulated cables

  • Author

    Katz, Carlos ; Walker, Michael

  • Author_Institution
    Cable Technol. Lab. Inc., New Brunswick, NJ, USA
  • Volume
    10
  • Issue
    1
  • fYear
    1995
  • fDate
    1/1/1995 12:00:00 AM
  • Firstpage
    25
  • Lastpage
    33
  • Abstract
    Data are provided from laboratory evaluations performed on ten 15 kV and five 35 kV ethylenepropylene copolymer rubber (EPR) feeder cables, made by one manufacturer and ranging in service age from 2 to 22 years. The evaluations consisted of visual examination of cable components, including the presence of water trees in the insulation and physical and electrical tests to establish changes which may have occurred in service. The data are used to establish an in-service rate of degradation for cables, up to 13 years in service, made with one type of EPR formulation. Based on an extrapolation of the breakdown voltage test results, it is expected that this type of cable will have a service life in excess of 30 years
  • Keywords
    ageing; electric breakdown; ethylene-propylene rubber; insulation testing; life testing; power cable insulation; trees (electrical); 15 kV; 2 to 22 y; 35 kV; EPR; breakdown voltage test; cable components; electrical tests; ethylene propylene rubber insulated cables; ethylenepropylene copolymer rubber; feeder cables; field aged power cables; in-service degradation rate; insulation; laboratory evaluations; physical tests; visual examination; water trees; Aging; Cable insulation; Dielectrics and electrical insulation; Insulation testing; Laboratories; Manufacturing; Paramagnetic resonance; Performance evaluation; Rubber; Trees - insulation;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.368419
  • Filename
    368419