• DocumentCode
    1248038
  • Title

    Reduced neutral XLPE cable design

  • Author

    Valli, G.F. ; Zawadzki, J.A. ; Orton, H.E.

  • Author_Institution
    B.C. Hydro & Power Authority, Vancouver, BC, Canada
  • Volume
    5
  • Issue
    2
  • fYear
    1990
  • fDate
    4/1/1990 12:00:00 AM
  • Firstpage
    794
  • Lastpage
    798
  • Abstract
    The authors describe the theoretical, laboratory, and economic analyses undertaken by B.C. Hydro to determine the optimum metallic concentric neutral design for its single-conductor 750 and 500 kcmil aluminum XLPE (cross-linked polyethylene) 15 kV and 25 kV insulated concentric-neutral-type feeder cables. The results suggest that reducing the cross-section area of this concentric neutral from the currently recognized industry standard of 20% of the central conductor to 7% results in an overall present-worth system cost saving of approximately $3 per conductor meter or approximately 22% of the cable first cost. The neutral configuration ultimately chosen to replace the previous standard 37#14 AWG wires was two 1-in×5 mil tinned copper tapes overlapped by 25%. Line voltage fault tests were run in the high-power laboratory on samples with various neutral configurations to confirm that they would successfully pass the worst-case fault duty of 10 kA for 20 cycles (i.e. .33 s) with no reclosing
  • Keywords
    cable insulation; cable testing; design engineering; organic insulating materials; polymers; power cables; 10 kA; 15 kV; 25 kV; XLPE; cable testing; cost saving; cross-linked polyethylene; design; fault tests; feeder cables; optimum metallic concentric neutral design; organic insulating materials; polymers; power cable insulation; standard; Aluminum; Cable insulation; Cables; Conductors; Copper; Costs; Polyethylene; Testing; Voltage; Wires;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.53085
  • Filename
    53085