DocumentCode :
1250710
Title :
Dielectric strength of SF6 insulation in EHV disconnectors
Author :
Lee, Hyeong-Ho ; Borin, V.N. ; Varivodov, V.N.
Author_Institution :
Korea Electrotechnol. Res. Inst., Changwon, South Korea
Volume :
4
Issue :
1
fYear :
1997
fDate :
2/1/1997 12:00:00 AM
Firstpage :
102
Lastpage :
107
Abstract :
A new method for the calculation of parameters of SF6 insulation for extra HV GIS disconnectors is given. This method is based on a new criterion for leader inception, which is connected with the value of the peripheral electric field near the boundary of the streamer zone. The presence of such a critical field is confirmed by analysis of experimental results and physical considerations
Keywords :
SF6 insulation; discharges (electric); electric strength; gas insulated switchgear; EHV GIS disconnectors; SF6; SF6 insulation; critical field; dielectric strength; inception precursor voltage; leader inception; micro-irregularities; peripheral electric field; streamer zone boundary; Conductivity; Corona; Dielectric breakdown; Dielectrics and electrical insulation; Electrodes; Electrons; Energy loss; Ionization; Nonuniform electric fields; Voltage;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/94.590876
Filename :
590876