• DocumentCode
    1252004
  • Title

    Optimal coordination of directional overcurrent relays considering definite time backup relaying

  • Author

    Pérez, Luis G. ; Urdaneta, Alberto J.

  • Author_Institution
    Univ. Simon Bolivar, Caracas, Venezuela
  • Volume
    14
  • Issue
    4
  • fYear
    1999
  • fDate
    10/1/1999 12:00:00 AM
  • Firstpage
    1276
  • Lastpage
    1284
  • Abstract
    A methodology is presented for the consideration of definite-time backup relays in the optimal coordination of directional overcurrent relays using linear programming. It is shown that the influence of considering second-zone distance relays and breaker failure relays impose important requirements for the determination of the time dial settings of directional overcurrent relays. The paper introduces a revised formulation of the optimization problem. Results are presented for the application of the methodology on a power system with 2 generators, 9 buses, 2 transformers and 7 transmission lines
  • Keywords
    linear programming; overcurrent protection; power system protection; relay protection; breaker failure relays; computer aided relay coordination; definite time backup relaying; directional overcurrent relays coordination; linear programming; power system protection; second-zone distance relays; Application software; Equations; Linear programming; Power generation; Power system protection; Power system relaying; Protective relaying; Relays; Topology; Transformers;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.796218
  • Filename
    796218