    Design and Application of a Low-Ratio High-Accuracy Split-Core Core-Balance Current Transformer

  • Author

    Das, J.C. ; Mullikin, Randy

  • Author_Institution
    AMEC E&C Services, Inc., Tucker, GA, USA
  • Volume
    46
  • Issue
    5
  • fYear
    2010
  • Firstpage
    1856
  • Lastpage
    1865
  • Abstract
    This paper describes the design and application of a split-core current transformer (CT) of large dimensions, specifically designed for mounting in a 13.8-kV switchgear cubical on the phase bus bars. Although split-core CTs of high current ratio are available, the authors believe that the core-balance CT described in this paper is unique, as no similar CT was readily available in the U.S./European market. Thus, there is no equivalent installation in the industry of the specifications described in this paper. The CT discussed in this paper was specifically designed to meet the requirements of dimensions and accuracy for sensitive ground fault and directional ground fault relaying.
  • Keywords
    current transformers; power markets; switchgear; European market; U.S. market; directional ground fault relaying; ground fault; phase bus bar; split core core balance current transformer; switchgear; Accuracy; Bars; Cables; Circuit faults; Circuit testing; Current transformers; Fault currents; Insulation; Pulp and paper industry; Relays; Thermal resistance; Transformer cores; Windings; CT saturation; Class-C and class-T accuracies; core-balance current transformers (CTs); split core;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2010.2059638
  • Filename
    5523988