Distribution transformer performance when subjected to steep front impulses
Author :
Burrage, L.M. ; Shaw, J.H. ; McConnell, B.W.
Author_Institution :
Cooper Ind. Inc., Franksville, WI, USA
Volume :
5
Issue :
2
fYear :
1990
fDate :
4/1/1990 12:00:00 AM
Firstpage :
984
Lastpage :
990
Abstract :
Arrester-protected pole-type distribution transformers were subjected to the combined stresses caused by the conducted steep front impulse and rated 60 Hz voltages. The results are compared with those of similar experiments on unenergized distribution transformers and with low-voltage impulse wave distribution results. It is concluded that (1) tank-mounted direct-connected arresters provide a high degree of protection to these transformers, (2) tank-mounted externally gapped or crossarm mounted arresters may not provide sufficient protection, and (3) internal transformer insulation system failures caused by the steep front impulse do not necessarily result in immediate catastrophic failures of the transformers
Keywords :
power transformers; 60 Hz; arrester-protected pole type distribution transformers; crossarm mounted arresters; internal transformer insulation system failures; steep front impulses; tank-mounted direct-connected arresters; Arresters; Cables; Electrical equipment industry; Low voltage; Power system protection; Power systems; Power transformer insulation; Power transformers; Pulse power systems; Surges;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.53111
Filename :
53111
Link To Document :
بازگشت