• DocumentCode
    1259169
  • Title

    Distribution transformer performance when subjected to steep front impulses

  • Author

    Burrage, L.M. ; Shaw, J.H. ; McConnell, B.W.

  • Author_Institution
    Cooper Ind. Inc., Franksville, WI, USA
  • Volume
    5
  • Issue
    2
  • fYear
    1990
  • fDate
    4/1/1990 12:00:00 AM
  • Firstpage
    984
  • Lastpage
    990
  • Abstract
    Arrester-protected pole-type distribution transformers were subjected to the combined stresses caused by the conducted steep front impulse and rated 60 Hz voltages. The results are compared with those of similar experiments on unenergized distribution transformers and with low-voltage impulse wave distribution results. It is concluded that (1) tank-mounted direct-connected arresters provide a high degree of protection to these transformers, (2) tank-mounted externally gapped or crossarm mounted arresters may not provide sufficient protection, and (3) internal transformer insulation system failures caused by the steep front impulse do not necessarily result in immediate catastrophic failures of the transformers
  • Keywords
    power transformers; 60 Hz; arrester-protected pole type distribution transformers; crossarm mounted arresters; internal transformer insulation system failures; steep front impulses; tank-mounted direct-connected arresters; Arresters; Cables; Electrical equipment industry; Low voltage; Power system protection; Power systems; Power transformer insulation; Power transformers; Pulse power systems; Surges;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.53111
  • Filename
    53111