Distribution transformer performance when subjected to steep front impulses
Author
Burrage, L.M. ; Shaw, J.H. ; McConnell, B.W.
Author_Institution
Cooper Ind. Inc., Franksville, WI, USA
Volume
5
Issue
2
fYear
1990
fDate
4/1/1990 12:00:00 AM
Firstpage
984
Lastpage
990
Abstract
Arrester-protected pole-type distribution transformers were subjected to the combined stresses caused by the conducted steep front impulse and rated 60 Hz voltages. The results are compared with those of similar experiments on unenergized distribution transformers and with low-voltage impulse wave distribution results. It is concluded that (1) tank-mounted direct-connected arresters provide a high degree of protection to these transformers, (2) tank-mounted externally gapped or crossarm mounted arresters may not provide sufficient protection, and (3) internal transformer insulation system failures caused by the steep front impulse do not necessarily result in immediate catastrophic failures of the transformers
Keywords
power transformers; 60 Hz; arrester-protected pole type distribution transformers; crossarm mounted arresters; internal transformer insulation system failures; steep front impulses; tank-mounted direct-connected arresters; Arresters; Cables; Electrical equipment industry; Low voltage; Power system protection; Power systems; Power transformer insulation; Power transformers; Pulse power systems; Surges;