    Transient overvoltages on a three terminal DC transmission system due to monopolar ground faults

  • Author

    Wrate, G.T. ; Tasinga, I.K. ; Low, S.S. ; Melvold, D.J. ; Thallam, R.S. ; Gerlach, D.W. ; Chang, J.Y.

  • Author_Institution
    Dept. of Water & Power, Los Angeles, CA, USA
  • Volume
    5
  • Issue
    2
  • fYear
    1990
  • fDate
    4/1/1990 12:00:00 AM
  • Firstpage
    1047
  • Lastpage
    1053
  • Abstract
    Transient overvoltages were investigated using the Electromagnetic Transients Program (EMTP) for a three-terminal DC transmission system. Pole-to-ground faults on a DC line were studied to investigate overvoltages on the healthy pole and also on the electrode lines. The effect of providing a metallic neutral conductor in one section of the three-terminal system was also studied, as was the sensitivity of the results to DC filter configuration and to neutral bus capacitance. It was found that the peak overvoltages for the DC line, especially near the converter stations, are sensitive to the DC filter configuration. The overvoltages near the converter stations were also found to be affected by the neutral bus capacitance
  • Keywords
    DC power transmission; electrical faults; overvoltage; transients; 3-terminal DC transmission systems; DC filter configuration; DC line; EMTP; Electromagnetic Transients Program; electrode lines; monopolar ground faults; neutral bus capacitance; pole-to-ground faults; transient overvoltages; Capacitance; Conductors; EMTP; Electrodes; Electromagnetic transients; Filters; HVDC transmission; Power system transients; Senior members; Surges;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.53120
  • Filename
    53120