An algorithm for standing phase angle reduction for power system restoration
Author :
Hazarika, D. ; Sinha, A.K.
Author_Institution :
Dept. of Electr. Eng., Indian Inst. of Technol., Kharagpur, India
Volume :
14
Issue :
4
fYear :
1999
fDate :
11/1/1999 12:00:00 AM
Firstpage :
1213
Lastpage :
1218
Abstract :
During power system restoration, it is necessary to check the phase angle between two buses before closing circuit breakers to connect a line between them. In case of large standing phase angle (SPA) difference the synchrocheck relay does not allow closing of the breaker for this line. Therefore, this SPA has to be reduced before attempting to connect the line. In this paper a new and fast method for reducing SPA is presented. For this purpose, the standing phase angle difference between two specific buses is represented in terms of sensitivity factors associated with the change in real power injections at the buses. The proposed method will act as a direct help for reducing excessive SPA difference between two buses to an acceptable limit
Keywords :
load shedding; power generation scheduling; power system restoration; circuit breakers closing; generation rescheduling; load shedding; phase angle checking; power system restoration; real power injections; sensitivity factors; standing phase angle reduction; synchrocheck relay; transmission line; AC generators; Circuit breakers; In vitro fertilization; Power engineering computing; Power generation; Power system analysis computing; Power system economics; Power system restoration; Power systems; Voltage;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/59.801875
Filename :
801875
Link To Document :
بازگشت