DocumentCode
1263878
Title
Power flow constrained harmonic analysis in AC-DC power systems
Author
Smith, B.C. ; Arrillaga, J.
Author_Institution
Canterbury Univ., Christchurch, New Zealand
Volume
14
Issue
4
fYear
1999
fDate
11/1/1999 12:00:00 AM
Firstpage
1251
Lastpage
1261
Abstract
When calculating noncharacteristic harmonics generated by an HVDC converter, unbalance in the AC system at fundamental frequency and all harmonics must be taken into account. This entails that a full three-phase load flow be part of the solution, as there is considerable distortion interaction between the load flow and the converter. To date, this has been achieved by iterating sequentially between the load flow and a harmonic converter model, in a type of decoupled method which is likely to suffer poor convergence. The decoupled method is implemented here, and convergence compared with a unified Newton solution of the load flow and converter models. Finally, the effect of not modelling the distortion interaction between the two systems is investigated
Keywords
HVDC power convertors; harmonic distortion; load flow; power system harmonics; power system interconnection; AC system fundamental frequency imbalance; AC-DC power systems; HVDC power converter; convergence; distortion interaction modelling; harmonic converter model; noncharacteristic harmonics; power flow constrained harmonic analysis; AC generators; Frequency conversion; Harmonic analysis; Load flow; Power generation; Power system analysis computing; Power system economics; Power system harmonics; Power system modeling; Voltage;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.801881
Filename
801881