• DocumentCode
    1263878
  • Title

    Power flow constrained harmonic analysis in AC-DC power systems

  • Author

    Smith, B.C. ; Arrillaga, J.

  • Author_Institution
    Canterbury Univ., Christchurch, New Zealand
  • Volume
    14
  • Issue
    4
  • fYear
    1999
  • fDate
    11/1/1999 12:00:00 AM
  • Firstpage
    1251
  • Lastpage
    1261
  • Abstract
    When calculating noncharacteristic harmonics generated by an HVDC converter, unbalance in the AC system at fundamental frequency and all harmonics must be taken into account. This entails that a full three-phase load flow be part of the solution, as there is considerable distortion interaction between the load flow and the converter. To date, this has been achieved by iterating sequentially between the load flow and a harmonic converter model, in a type of decoupled method which is likely to suffer poor convergence. The decoupled method is implemented here, and convergence compared with a unified Newton solution of the load flow and converter models. Finally, the effect of not modelling the distortion interaction between the two systems is investigated
  • Keywords
    HVDC power convertors; harmonic distortion; load flow; power system harmonics; power system interconnection; AC system fundamental frequency imbalance; AC-DC power systems; HVDC power converter; convergence; distortion interaction modelling; harmonic converter model; noncharacteristic harmonics; power flow constrained harmonic analysis; AC generators; Frequency conversion; Harmonic analysis; Load flow; Power generation; Power system analysis computing; Power system economics; Power system harmonics; Power system modeling; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.801881
  • Filename