• DocumentCode
    1263963
  • Title

    The development of equivalent system technique for deriving an energy function reflecting transfer conductances

  • Author

    Moon, Young-Hyun ; Cho, Byoung-Hoon ; Rho, Tae-Hoon ; Choi, Byoung-Kon

  • Author_Institution
    Dept. of Electr. Eng., Yonsei Univ., Seoul, South Korea
  • Volume
    14
  • Issue
    4
  • fYear
    1999
  • fDate
    11/1/1999 12:00:00 AM
  • Firstpage
    1335
  • Lastpage
    1341
  • Abstract
    This paper shows that a well-defined energy function can be developed to reflect the transfer conductances for multi-machine power systems under an assumption that all transmission lines have uniform R/X ratios. The energy function is derived by introducing a pure reactive equivalent system for the given system. In this study, a static energy function reflecting transfer conductances is also derived as well as the transient energy function. The proposed static energy function is applied to voltage stability analysis and tested for various sample systems. The test results show that the accuracy of voltage stability analysis can be considerably improved by reflecting transfer conductances into the energy function
  • Keywords
    electric admittance; power system transient stability; power transmission lines; equivalent system technique; multi-machine power systems; static energy function; transfer conductances; transient energy function; transmission lines; uniform R/X ratios; voltage stability analysis; well-defined energy function derivation; Moon; Power system analysis computing; Power system simulation; Power system stability; Power system transients; Power transmission lines; Stability analysis; System testing; Transmission line theory; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.801893
  • Filename
    801893