• DocumentCode
    1266046
  • Title

    The use of single-core lead-covered and armoured cables for alternating currents

  • Author

    Cramp, W.

  • Volume
    63
  • Issue
    340
  • fYear
    1925
  • fDate
    4/1/1925 12:00:00 AM
  • Firstpage
    379
  • Lastpage
    383
  • Abstract
    In a previous paper Miss Calderwood and the present author examined the losses in the lead sheath of a single-core cable when carrying an alternating current, and concluded that, provided the outgoing and return cables were laid within a certain limiting distance of one another, no difficulty would arise due to eddy currents in the sheaths at normal frequencies. In the present paper this work is extended to cover the case of single-core cables that are both lead-covered and armoured. A theoretical investigation of the reactances and losses is carried out and is checked against the actual test figures obtained by Harvey and Busby. It is shown :¿ 1. That the flux in the armour, the reactance due to that flux, and the appropriate hysteresis and eddy losses can all be approximately predetermined. 2. That for low-tension transmission, lead-covered and armoured cables are impracticable with armouring as at present constructed. 3. That the use of such cables for e.h.t. transmission is not precluded by the magnetic conditions introduced by the armour, and consequently such cables are practicable. There would, however, be some difficulties to be overcome due to large capacity currents when the transmission distance is great.
  • fLanguage
    English
  • Journal_Title
    Electrical Engineers, Journal of the Institution of
  • Publisher
    iet
  • Type

    jour

  • DOI
    10.1049/jiee-1.1925.0042
  • Filename
    5313532