• DocumentCode
    1266317
  • Title

    Flashover vulnerability of transmission and distribution lines to high-altitude electromagnetic pulse (HEMP)

  • Author

    Kruse, V.J. ; Tesche, F.M. ; Liu, T.K. ; Barnes, P.R.

  • Author_Institution
    Westinghouse Electr. Corp., Pittsburgh, PA, USA
  • Volume
    5
  • Issue
    2
  • fYear
    1990
  • fDate
    4/1/1990 12:00:00 AM
  • Firstpage
    1164
  • Lastpage
    1169
  • Abstract
    The vulnerability of transmission and distribution lines to flashover from the electromagnetic pulse generated by a nuclear detonation 400 km above the Earth is estimated. The analysis consists of determining the cumulative probability of induced voltage on three-phase lines, including shield and neutral conductors, for four operating voltages and then comparing these stresses to estimates of line insulation strength. The 12 kV line is shown to be vulnerable to HEMP-induced flashover. The 69 kV line is marginally vulnerable to HEMP-induced flashover, but only the minimum-insulation designs in current use are susceptible, and the probability of flashover for those designs is minimal. The 500 and 230 kV lines are invulnerable to HEMP-induced flashover for all HEMP field levels considered
  • Keywords
    electromagnetic pulse; flashover; power transmission lines; 12 kV; 230 kV; 500 kV; 69 kV; HEMP; distribution lines; flashover vulnerability; high-altitude electromagnetic pulse; induced voltage; line insulation strength; neutral conductors; nuclear detonation; shield conductors; three-phase lines; transmission lines; EMP radiation effects; Earth; Flashover; Insulation; Lighting; Polarization; Power system simulation; Shape; Stress; US Department of Energy;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.53136
  • Filename
    53136