A ground-based sensor for the detection of transmission line conductor motion
Author
Jacobs, M.L. ; Vaselaar, G.A.
Author_Institution
Bur. of Reclamation, Denver, CO, USA
Volume
5
Issue
2
fYear
1990
fDate
4/1/1990 12:00:00 AM
Firstpage
1170
Lastpage
1174
Abstract
A novel lower-cost method of detecting transmission line conductor motion has been developed. The detector is ground based and can be installed by two people with no line outage or physical connection to the transmission line structure. Detection sensitivity is approximately 0.3 m (1 ft) p-p (peak-to-peak). Field testing has shown that the detector can detect several modes of conductor motion, including both single and double-loop motion, as well conductor blowout conditions. It is concluded that this detector can greatly aid in conductor motion data gathering with reduced cost and enhanced personnel safety over alternate approaches
Keywords
electric sensing devices; overhead line mechanical characteristics; position measurement; conductor blowout conditions; detection sensitivity; ground-based sensor; motion detection; personnel safety; transmission line conductor motion; Conductors; Detectors; Frequency; Laboratories; Motion detection; Power transmission lines; Transmission line measurements; Transmission line theory; Transmission lines; Voltage;