• DocumentCode
    1266519
  • Title

    Over-voltage on transmission systems due to dropping of load

  • Author

    Burnham, E.J.

  • Author_Institution
    Central Station Engineering Dept., General Electric Company, Schenectady, New York
  • Volume
    44
  • Issue
    6
  • fYear
    1925
  • fDate
    6/1/1925 12:00:00 AM
  • Firstpage
    579
  • Lastpage
    587
  • Abstract
    When a water wheel-driven generator, or a hydroelectric station, loses all or a large part of its load, the voltage rises more rapidly and to a greater extent than has been generally realized. The purpose of this paper is to show the manner in which the voltage will rise under different conditions, and a method of calculating the voltage rise of a water wheel-driven generator when load is lost. The results of a large number of tests are given showing the rise in voltage on an 8500-kv-a., 6600-volt water wheel generator when load was tripped under several different conditions at three different places, namely; at the generator, on the high-voltage side of a transformer bank, and at a substation forty miles away. As it is not considered good practise to subject a transmission system to high over-voltages, consideration is given to methods of checking the voltage rise by use of relays as soon as possible after load has been dropped.