DocumentCode :
1267274
Title :
Abridgment of effect of surges on transformer windings
Author :
Hodnette, J.
Author_Institution :
Westinghouse Electric & Mfg. Co., Sharon, Pa.
Volume :
48
Issue :
11
fYear :
1929
Firstpage :
829
Lastpage :
832
Abstract :
A study has been made of the reaction of transformer windings in grounded neutral systems when subjected to transient voltage surges such as exist on normally insulated lines. Measurements of the voltage distribution throughout the windings between various elements and to ground were effected by means of a cold cathode type cathode ray oscillograph and sphere-gaps. An estimate of the stresses occurring in transformers due to the voltages occurring on transmission systems is made, basing them on the most recent data obtainable. The data indicate that the worst stresses, both within the winding and to ground, are in the vicinity of the line coil.
fLanguage :
English
Journal_Title :
A.I.E.E., Journal of the
Publisher :
ieee
ISSN :
0095-9804
Type :
jour
DOI :
10.1109/JAIEE.1929.6535946
Filename :
6535946
Link To Document :
بازگشت