• DocumentCode
    1267452
  • Title

    Experimental analysis of stability and power limitations

  • Author

    Evans, Richard David ; Bergvall, R.C.

  • Author_Institution
    Westinghouse Electric & Manufacturing Co.
  • Volume
    43
  • Issue
    4
  • fYear
    1924
  • fDate
    4/1/1924 12:00:00 AM
  • Firstpage
    329
  • Lastpage
    340
  • Abstract
    A method of determining the power limit of a transmission system taking into account the characteristics of the synchronous condensers and load in conjunction with those of the transmission line is described. The power limit of a transmission system divided into two sections by an intermediate synchronous condenser station is determined and compared that of the same system without the condenser station at the mid-point. The theory was checked by shop tests on in artificial transmission system of sufficient capacity so that accurate results could be obtained. Tests were also made on voltage stability, hunting and the effect of short circuits causing the system to pull out of synchronism.
  • fLanguage
    English
  • Journal_Title
    A.I.E.E., Journal of the
  • Publisher
    ieee
  • ISSN
    0095-9804
  • Type

    jour

  • DOI
    10.1109/JAIEE.1924.6535977
  • Filename
    6535977