• DocumentCode
    1270650
  • Title

    Single-pole short-circuit interruption of molded-case circuit breakers

  • Author

    Gregory, George D.

  • Author_Institution
    Square D Co., Cedar Rapids, IA, USA
  • Volume
    35
  • Issue
    6
  • fYear
    1999
  • Firstpage
    1265
  • Lastpage
    1270
  • Abstract
    Short-circuit tests of individual poles of molded-case circuit breakers are required under North American industry standards. Test current is intentionally at a limited fault availability level rather than at the interrupting rating of the circuit breaker. This paper clarifies the single-pole test requirements. It then examines the potential fault conditions under a variety of systems and provides application guidelines considering the potential fault conditions
  • Keywords
    circuit breakers; electrical faults; interrupters; switchgear testing; North American industry standards; application guidelines; fault availability level; interrupting rating; moulded-case circuit breakers; potential fault conditions; single-pole short-circuit interruption tests; single-pole test requirements; Circuit breakers; Circuit faults; Circuit testing; Conductors; Grounding; Guidelines; Leg; National electric code; System testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/28.806037
  • Filename
    806037