Title :
Influence of Reactors on Input Harmonics of Variable Frequency Drives
Author :
Xiaodong Liang ; Ilochonwu, O. ; Lim, Jungyoul
Author_Institution :
Edmonton Product Center, Schlumberger, Edmonton, AB, Canada
Abstract :
AC line reactors and dc link reactors are widely used in variable frequency drives (VFDs) to improve the drive performance such as reducing input harmonics, improving the input power factor, and protecting the drives from surges, etc. The effectiveness of both types of reactors in reducing input harmonics is affected by many factors, including the loading of the drives and the system source impedance. In this paper, a simulation is conducted to investigate the influence of such factors. Two power distribution systems with VFDs as the dominant loads in the oil field are used as the case studies. The rules to evaluate the needs and effectiveness using ac line or dc link reactors are proposed for practical applications.
Keywords :
electric impedance; power harmonic filters; reactors (electric); variable speed drives; AC line reactors; VFD; dc link reactors; harmonic suppression; power distribution systems; system source impedance; variable frequency drives; Harmonic analysis; Impedance; Inductance; Inductors; Loading; Power system harmonics; AC line reactor; dc link reactor; input harmonics; power source impedance;
Journal_Title :
Industry Applications, IEEE Transactions on
DOI :