Abstract :
During short line fault (SLF) tests on three poles of a 72.5 kV, 31.5 kA, 60 Hz SF6 puffer circuit breaker, some remarkably large post-arc currents were measured. For all the measurements performed on the three poles of the specific breaker, no physical post-arc currents could be detected in the measurement data, except for two cases. Both ´post-arc currents´ occurred as a last successful interruption of a circuit breaker pole. After these specific interruptions, the circuit breaker poles were degraded so much that only reignitions occurred. In order to verify the observed ´post-arc currents´, computations are made based on the more accurate voltage measurements
Keywords :
SF6 insulation; circuit-breaking arcs; gas blast circuit breakers; 31.5 kA; 60 Hz; 72.5 kV; SF6; SF6 puffer circuit breaker pole; post-arc current reconstruction; short line fault test; voltage measurement;