• DocumentCode
    1273044
  • Title

    A-G. network relay characteristics

  • Author

    Blake, D.K.

  • Author_Institution
    Central Station Engineering Dept., General Electric Co., Schenectady, N. Y.
  • Volume
    46
  • Issue
    4
  • fYear
    1927
  • fDate
    4/1/1927 12:00:00 AM
  • Firstpage
    361
  • Lastpage
    369
  • Abstract
    This paper discusses the required characteristics of relays for use with a low-voltage automatic network circuit breaker. The relay performs the two functions of tripping and reclosing the circuit breaker. The characteristic required for each function is discussed. The major part of the paper is given to a discussion of the reclosing function because of the danger of “pumping” caused by cable charging currents and various combinations of induction regulators and transformer connections. Emphasis is placed on the suitability of relays consisting of watthom meter characteristics, construction and adjustments, involving only a different current coil and the replacement of the recording mechanism by standard relay contacts.
  • fLanguage
    English
  • Journal_Title
    A.I.E.E., Journal of the
  • Publisher
    ieee
  • ISSN
    0095-9804
  • Type

    jour

  • DOI
    10.1109/JAIEE.1927.6536945
  • Filename