• DocumentCode
    1273409
  • Title

    A ready method of measuring the voltage ratio and phase angle of high-voltage transformers

  • Author

    Yoganandam, G.

  • Volume
    68
  • Issue
    397
  • fYear
    1930
  • fDate
    1/1/1930 12:00:00 AM
  • Firstpage
    192
  • Lastpage
    193
  • Abstract
    A quick and ready method of measuring the ratio and phase angle of high-voltage transformers is described in which the well-known high-voltage Schering bridge is employed. Formulÿ for the voltage ratio and phase angle are given, together with expresssions for the sensitivity of the bridge. The accuracy obtained by the method meets the requirements of all industrial tests as well as of research work.
  • Keywords
    transformers;
  • fLanguage
    English
  • Journal_Title
    Electrical Engineers, Journal of the Institution of
  • Publisher
    iet
  • Type

    jour

  • DOI
    10.1049/jiee-1.1930.0012
  • Filename
    5315354