• DocumentCode
    1273450
  • Title

    Grounding System in Marinas: The Microsystem Approach

  • Author

    Parise, G. ; Parise, Luigi ; Mitolo, Massimo

  • Author_Institution
    Electr. Eng. Dept., Univ. of Rome, Rome, Italy
  • Volume
    47
  • Issue
    5
  • fYear
    2011
  • Firstpage
    2204
  • Lastpage
    2209
  • Abstract
    The microsystem design approach of electric systems has the purpose to improve their safety, maintenance, operation, and reliability. The microsystem design approach can be applied to the case of marinas, where pleasure craft may be moored. Marinas require a structured architecture for the shore electrical power distribution system, which supplies power to distributed loads. In addition, the design must provide for solutions to electrical hazards, as possible stray currents circulating through the earth and the water. The island-grounding system, which utilizes separation transformers grounded at the midpoint of their secondary sides, allows to supply loads divided into “islands” as independent electrical areas. This distribution system is an effective way to protect persons from shock hazards in installations with contained demand load and to greatly limit electrical interferences among systems. According to these authors, the TN-island-grounding system is the best option to supply shore power to pleasure craft in marinas. This paper substantiates that the TN-island-grounding system allows the development of “hybrid” solutions that lend themselves to the application of either the National Electrical Code, USA, or the International Electrotechnical Commission-European Union codes and standards. This important achievement would contribute to eliminate technical obstacles and discourage market barriers still existing worldwide.
  • Keywords
    earthing; electrical safety; offshore installations; power distribution protection; power transformers; TN-island-grounding system; electrical hazards; electrical interferences; marinas; microsystem design; separation transformers; shock hazards; shore electrical power distribution system; stray currents; Boats; Circuit faults; Conductors; Grounding; Power transformer insulation; Safety; Windings; Earth; exposed conductive part; extraneous conductive part; ground; ground-fault circuit interrupter (GFCI); neutral; residual-current devices (RCDs); single-phase line-to-ground fault; voltage rise;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2011.2162052
  • Filename
    5954179