DocumentCode :
1275182
Title :
Simulation of forces and 3-D field arising during power autotransformer fault due to electric arc in HV winding
Author :
Zakrzewski, K. ; Tomczuk, B. ; Koteras, D.
Author_Institution :
Inst. of Electr. Machines & Transformers, Tech. Univ. Lodz, Poland
Volume :
38
Issue :
2
fYear :
2002
fDate :
3/1/2002 12:00:00 AM
Firstpage :
1153
Lastpage :
1156
Abstract :
Forces and three-dimensional magnetic fields in high-voltage winding due to an internal short circuit in a power autotransformer are calculated with the computer package OPERA 3D. The considered damage was caused by an electric arc. The materialized deformation of the winding part confirms the simulation results
Keywords :
arcs (electric); autotransformers; electrical faults; magnetic fields; magnetic forces; power engineering computing; short-circuit currents; transformer windings; 3D field simulation; OPERA computer package; electric arc; forces; high-voltage winding; internal short circuit; materialized deformation; power autotransformer; short circuit; three-dimensional magnetic fields; Circuit faults; Circuit simulation; Coils; Electrodynamics; Magnetic analysis; Magnetic circuits; Magnetic fields; Numerical models; Transformers; Wires;