DocumentCode :
127548
Title :
Proving viability of line current differential over packet switched networks
Author :
Roesler, Silvio ; Lobo, Ryan
fYear :
2014
fDate :
March 31 2014-April 3 2014
Firstpage :
542
Lastpage :
551
Abstract :
Deploying line current differential protection over Ethernet packet switched transport is more than just making the connections, as the application demands certain deterministic characteristics from the communication channel. Packet switched traffic by its very nature of statistical multiplexing is subject to variances in propagation time due to queuing delays, which can impact the performance of line current differential schemes that are dependent on channel-based synchronization. This paper details the results of testing a line current differential system on a Multiprotocol Label Switching (MPLS) based Ethernet packet switched network. A variety of simulations were performed in order to determine if reliable protection could be achieved in such a network. Protection times were measured and reliability assessed. Impacts of a number of potential threats were established and overall protection performance was evaluated. Details on engineering the network to meet the Reliability, Selectivity, Coordination, Sensitivity, and Speed requirements of a line current differential system are provided.
Keywords :
local area networks; multiprotocol label switching; power cables; power engineering computing; power system protection; power system reliability; queueing theory; statistical multiplexing; switching networks; synchronisation; telecommunication channels; telecommunication traffic; Ethernet packet switched transport network; MPLS; channel- based synchronization; communication channel; deterministic characteristics; multiprotocol label switching; packet switched traffic; power line current differential protection system; queuing delay; reliability requirement; statistical multiplexing; Communication channels; Delays; Relays; Sensitivity; Switches; Synchronization; Time division multiplexing; Line Current Differential Protection; Packet Switched Networks; Teleprotection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Protective Relay Engineers, 2014 67th Annual Conference for
Conference_Location :
College Station, TX
Print_ISBN :
978-1-4799-4740-9
Type :
conf
DOI :
10.1109/CPRE.2014.6799026
Filename :
6799026
Link To Document :
بازگشت