DocumentCode :
1275484
Title :
Current-transformer testing
Author :
Arnold, A.H.M.
Volume :
74
Issue :
449
fYear :
1934
fDate :
5/1/1934 12:00:00 AM
Firstpage :
424
Lastpage :
437
Abstract :
A method of testing current transformers by comparison with standard current transformers is described. The apparatus has three ranges. The most sensitive range is capable of measuring ratio differences up to 5 parts in 10000 with an accuracy of approximately 1 part in 1000000, and phase angles up to 2.5 minutes with an accuracy of approximately 0.01 minute. The other two ranges are respectively 10 and 100 times as great, and the sensitivity is correspondingly reduced. The design and construction of suitable standard current-transformers to cover ratios from 5/5 up to 12000/5 are described, and the methods of calibrating these transformers to an accuracy of approximately 2 parts in 100000 for ratio and 0.1 minute for phase angle are outlined.
Keywords :
transformers;
fLanguage :
English
Journal_Title :
Electrical Engineers, Journal of the Institution of
Publisher :
iet
Type :
jour
DOI :
10.1049/jiee-1.1934.0064
Filename :
5315796
Link To Document :