Abstract :
Principles and applications of series capacitor banks and shunt reactors are first introduced. Then, the impacts of these apparatus on power systems are reviewed, including the behaviors of shunt reactors in the normal and fault conditions, the behaviors of series capacitor banks under the fault conditions. The effects of these apparatus on the line differential protection are particularly discussed. Challenges of relay applications are investigated with the emphasis on: advantages and disadvantages of including or excluding reactors in the 87L protection zone, solutions to compensate charging current, switching reactors in and out, voltage and current inversion of capacitor banks, sub-harmonic frequency transients, and effects of MOV conducting. In order to demonstrate challenges of the relay application, a long transmission line is studied, where two series capacitor banks are installed at approximately one third intervals on the transmission line and two shunt reactor banks are installed at both ends. Two configuration schemes are presented. Arrangement of the line current differential communications channels to achieve maximum security and dependability is discussed. The settings selection of the line current differential relays is discussed in detail. A simple method to calculate charging current compensation settings for line differential protection is described as well.
Keywords :
compensation; power capacitors; power system harmonics; power system security; power transmission faults; power transmission lines; power transmission protection; relay protection; MOV; charging current compensation; current inversion; line current differential communication channel; line current differential relay protection; line differential protection; long transmission line; power system fault; security; series capacitor bank; shunt reactor; subharmonic frequency transient; voltage inversion; Inductors; Switches; Line Current Differential Relay; Series Capacitor Bank; Shunt Reactor;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Protective Relay Engineers, 2014 67th Annual Conference for
Conference_Location :
College Station, TX
Print_ISBN :
978-1-4799-4740-9
Type :
conf
DOI :
10.1109/CPRE.2014.6799034
Filename :
6799034
Link To Document :
بازگشت