DocumentCode :
1275891
Title :
Synthetic Pressure Relief Testing of HV Metal Oxide Arresters
Author :
Latour, Yves ; St-Jean, Guy ; Petit, André ; Huynh, Hieu
Author_Institution :
IREQ (Institut de recherche d´´Hydro-Qu??bec), Varennes, Qu??bec, Canada
Issue :
12
fYear :
1985
Firstpage :
58
Lastpage :
59
Abstract :
This paper describes a new method of testing metal oxide surge arresters for HV applications. As in the case of circuit-breaker testing, this so-called synthetic method uses two separate sources, namely a high-voltage source (precharged capacitors) and a high-current source (60-Hz network). To the authors´ knowledge, this is the first time that the synthetic testing of surge arresters has been experimentally demonstrated. For the purpose, a 25-kA (asymmetrical) short circuit was produced without the aid of a fuse wire and maintained for 0.2 s (12 cycles). This type of testing allows a tenfold increase in the power-frequency (60-Hz) capacity of a test station.
Keywords :
Arresters; Capacitors; Circuit testing; Fuses; Laboratories; Metals; Performance evaluation; Regulators; Substations; Surge protection; Surges; Switches; Testing; Voltage; Wire;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.1985.5528643
Filename :
5528643
Link To Document :
بازگشت