DocumentCode :
1275990
Title :
Equivalent heat circuit based power transformer thermal model
Author :
Tang, W.H. ; Wu, Q.H. ; Richardson, Z.J.
Author_Institution :
Dept. of Electr. Eng. & Electron., Liverpool Univ., UK
Volume :
149
Issue :
2
fYear :
2002
fDate :
3/1/2002 12:00:00 AM
Firstpage :
87
Lastpage :
92
Abstract :
An equivalent heat circuit based thermal model of oil-immersed power transformers and a methodology for model construction using intelligent learning based on real-world data are presented. The proposed thermal model is established to calculate the real-time temperatures of the main parts of a natural oil, natural air (ONAN) and forced oil, forced air (OFAF) cooled power transformer, which is based on the principles of heat exchange and electric circuit laws. A genetic algorithm is used as a search method, based on a few onsite measurements, to determine the thermal model parameters.
Keywords :
cooling; power transformers; thermal analysis; transformer oil; equivalent heat circuit; forced air cooling; forced oil cooling; genetic algorithm; heat exchange; intelligent learning; model construction; natural air cooling; natural oil cooling; oil-immersed power transformers; power transformer thermal model; real-time temperatures natural oil; search method;
fLanguage :
English
Journal_Title :
Electric Power Applications, IEE Proceedings
Publisher :
iet
ISSN :
1350-2352
Type :
jour
DOI :
10.1049/ip-epa:20020290
Filename :
997798
Link To Document :
بازگشت