DocumentCode :
1277370
Title :
Abridgment of precautions against stray-field errors in measurements with large alternating currents
Author :
Silsbee, Francis B.
Author_Institution :
Physicist, Bureau of Standards
Volume :
48
Issue :
6
fYear :
1929
fDate :
6/1/1929 12:00:00 AM
Firstpage :
447
Lastpage :
450
Abstract :
In electric power stations it is often necessary to make accurate measurements of current or power when the instruments are located near to the cables carrying large alternating currents. The magnetic field produced by these currents may constitute a serious source of error in the measurements unless careful precautions are taken to guard against such disturbing effects. This paper summarizes the various principles and methods for detecting and minimizing the errors which may arise from this source. The principal methods are: (1) To so arrange the cables carrying the large currents that they produce as little stray magnetic effect as possible; (2) to use instruments of the shielded or of the astatic type; (3) to repeat readings with the instrument connections reversed; and (4) to avoid all loops in the connecting leads.
fLanguage :
English
Journal_Title :
A.I.E.E., Journal of the
Publisher :
ieee
ISSN :
0095-9804
Type :
jour
DOI :
10.1109/JAIEE.1929.6537701
Filename :
6537701
Link To Document :
بازگشت